- Abstract
The main aim of this study was to investigate occupational exposure to electric fields, and current densities and contact currents associated with tasks at air-insulated 110 kV substations and analyze if the action value of EU Directive 2004/40/EC was exceeded. Four workers volunteered to simulate the following tasks: Task (A) maintenance of an operating device of a disconnector at ground or floor level, Task (B) maintenance of an operating device of a circuit breaker at ground or floor level, Task (C) breaker head maintenance from a man hoist, and Task (D) maintenance of an operating device of a circuit breaker from a service platform. The highest maximum average current density in the neck was 1.8 mA/m(2) (calculated internal electric field 9.0-18.0 mV/m) and the highest contact current was 79.4 µA. All measured values at substations were lower than the limit value (10 mA/m(2)) of the EU Directive 2004/40/EC and the 2010 basic restrictions (0.1 and 0.8 V/m for central nervous system tissues of the head, and all tissues of the head and body, respectively) of the International Commission on Non-Ionizing Radiation Protection (ICNIRP).
- Publication
Bioelectromagnetics, 2012, Vol 33, Issue 5, p438
- ISSN
1521-186X
- Publication type
Journal Article
- DOI