- Title
Control with Building Mass -- Part II: Simulation.
- Authors
Armstrong, Peter R.; Leeb, Steven B.; Norford, Leslie K.
- Abstract
Reductions in building peak electrical demand can be achieved by incorporating building-specific models of thermal dynamics into controllers that will implement short-term peak-period curtailment of HVAC capacity or pre-cool the building prior to peak-period cutbacks to increase the magnitude and duration of the load reduction. The same building-specific model can be used to effect energy savings by providing optimal-start control or optimal-pre-cooling control during unoccupied hours. Control logic was developed for pre-cooling with a central HVAC plant equipped with an air-side economizer. Measurement-based estimates were made of chiller performance and internal-gains schedules. The general transient-thermal-response model of the companion paper (Armstrong et al. 2006) was then used to determine building-specific thermal response and estimate the seasonal benefits of several peak-shifting and night-cooling strategies in the office building. Simulations showed a 30% to 60% reduction in seasonal mechanical cooling loads in the office building due to night cooling.
- Subjects
UNITED States; OFFICE buildings; TEMPERATURE; TEMPERATURE measurements; THERMAL properties of buildings; AIR conditioning; VENTILATION; COOLING; HEATING &; ventilation industry
- Publication
ASHRAE Transactions, 2006, Vol 112, Issue 1, p462
- ISSN
0001-2505
- Publication type
Article