Challenges in achieving a high indoor air quality in an educational building.
- Authors
Vartires, Andreea; Damian, Andrei; Olariu, Andrei; Istrate, Andrei; Catalina, Tiberiu; Zorilă, Elena
- Abstract
Achieving a good indoor air quality in already built schools has been a challenge during the last decades. Different solutions have been proposed as an alternative to natural ventilation by opening windows. In this article we propose a simpler approach but yet effective to solve the problem. Using hybrid ventilation between hygroscopic air vent and a window fan can reduce drastically the indoor pollution. In fact, during the experimental campaign we have measured and calculated lower CO2 levels (aprox.1200 ppm) while in the non-ventilated classroom these values were approaching 2500 ppm. The humidity was also a parameter that needed to be monitored as it can influence the indoor environment. The calculations demonstrated that for 30 pupils in a classroom an airflow of 600 m3/h is the ideal solution.
- Subjects
INDOOR air quality; HEATING &; ventilation of school buildings; SCHOOLS &; the environment; WINDOW design &; construction; HUMIDITY; AIR flow
- Publication
Romanian Journal of Civil Engineering / Revista Română de Inginerie Civilă, 2018, Vol 9, Issue 1, p28