Pressure Losses in 12", 14", and 16" Non-Metallic Flexible Ducts with Compression and Sag.
- Authors
Culp, Charles; Cantrill, David
- Abstract
A study was conducted to measure air pressure loss in nonmetallic flexible ducts and included 12" (305 mm), 14" (356 mm) and 16" (406 mm) diameter ducts on a flat surface and also positioned over joists on 24" (610 mm) centers. For this study, flexible duct compression configurations were fully stretched and 4%, 15%, 30% and 45% compressed. Measurements were performed at each compression. All tests were performed in conformance to ASHRAE 120-1999, Methods of Testing to Determine Flow Resistance of HVAC Air Ducts and Fittings (ASHRAE 1999) with a positive pressure, blow-through configuration. The data from this study exhibited higher pressure loss than prior Air Conditioning Contractors of America (ACCA) or ASHRAE data. Measured pressure losses were 2 to 13 times higher than round steel ducts.