- Title
Lightning Trip-Out of 150 kV Transmission Line: a Case Study.
- Authors
Warmi, Yusreni; Koji Michishita
- Abstract
In this paper, the lightning performance of the 150 kV transmission line in West Sumatra, Indonesia, is studied in details, showing that the lightning trip-out rate depends on the tower-footing resistance and the length of an arcing horn gap. The observed trip-out rate higher than 20 trip-outs/100 km-year is in good agreement with the results of the simulation by the IEEE FLASH program by using the so-called impulse resistance. The dependency of the trip-out rate on the arm location fairly well agrees with the rate estimated by the IEEE method too.
- Subjects
ELECTRIC lines; LIGHTNING; CIRCUIT-breaking arcs; ADOBE Flash (Computer software); IMPULSE (Physics)
- Publication
International Review of Electrical Engineering, 2017, Vol 12, Issue 3, p260
- ISSN
1827-6660
- Publication type
Article
- DOI
10.15866/iree.v12i3.12233